Learning Advanced Features
Adv
anc
ed
Feat
ur
es
241
Code
Description
CON-53 Torque Lmt Src
Sets the input source for the torque limit function. The torque limit
function is used to limit the output to adjust the torque reference.
Setting
Description
0
Keypad-1
Sets the torque limit using the keypad (up to
200% of the motor rated torque).
1
Keypad-2
2
V1
Sets the torque limit using the analog terminals.
3
I1
6
Int 485
Sets the torque limit using the built-in 485
communication device.
IN-02 Torque at 100%
Sets the torque limit values for the analog input.
If CON-53 is set to
“
2 (V1)
”
and IN-02 is set to
“
200%
”
, the torque limit
becomes 200% when 10 V input is supplied to V1.*
(*Applies only if all V1 function parameters use default setting values.)
When any device other than the keypad is selected as the torque limit
input source, set CNF-21
–
23 to
“
21 (Torque Limit)
”
.
CON-33 FWD +Trq Lmt
CON-34 FWD
–
Trq Lmt
CON-35 REV +Trq Lmt
CON-36 REV
–
Trq Lmt
Sets the direction of the torque limit when CON-53 is set to
“
0 (Keypad-
1)
”
or
“
1 (Keypad-2)
”
. The torque limit can be set up to 200% of the
motor rated torque.
Setting
Description
FWD +Trq Lmt Sets the torque limit for FX motoring operation.
FWD
–
Trq Lmt
Sets the torque limit for FX regenerating operation.
REV +Trq Lmt
Sets the torque limit for RX motoring operation.
REV
–
Trq Lmt
Sets the torque limit for RX regenerating operation.
CON-58 Trq Bias Src
Selects the input source for the offset setting to be added to the torque
reference.
Setting
Description
0
Keypad-1
Sets the torque bias using the keypad (-120%
–
+120%, set at CON-59).
1
Keypad-2
2
V1
Sets the torque bias using the analog terminals.
(-120%
–
+120%, set at CON-59).
The setting can be viewed in monitor mode. Set
CFG-06
–
08 to
“
21 (Torque bias)
”
.
3
I1
CON-59 Torque Bias
Sets the torque bias value between -120%
–
+120%.
IN-65
–
75 Px Define
Sets one of the multi-function terminals to
“
48 (Trq Bias)
”
. Torque bias
input via the keypad or analog input is applied only when this multi-
function terminal is on.
CON-60 Trq BiasFF
Sets the compensation volume to add to the bias to make up for the
loss caused by motor rotation. Negative (-) values diminish the torque
bias.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...