Learning Advanced Features
204
When you press the [MULTI] key,
“J”
is displayed on the keypad indicating that a jog operation
via the keypad is available. Press and hold the [FWD] or [REV] key to perform forward or reverse
jog operations. Jog operations stop when you lift your finger from the [FWD] or [REV] key on
the keypad.
8.3
Up/down Operation
The acc/dec time can be controlled via the input at the multi-function terminal block. The up-
down operation can be applied easily to a system that uses the upper-lower limit switch signals
(such as those of a flow meter) for acc/dec commands.
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
ADV
65
Up/down operation
frequency save
U/D Save
Mode
1
Yes
0
–
1
-
85
Up/down mode Sel U/D Mode Sel
0
U/D Normal
0:U/D Normal
1:U/D Step
2:U/D
Step+Norm
-
86
Up/down Step
freqency
U/D Step Freq -
0
0-maximum
frequency
Hz
IN
65
–
75
Px terminal
configuration
Px Define
(Px: P1
–
P8
[optional:
P9
–
P11])
17 Up
0
–
51
-
18 Down
19 U/D Save
20 U/D Clear
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...