Learning Advanced Features
262
Cooling Fan Control Detail Settings
Code
Description
ADV-64 Fan
Control
Settings
Description
0
During Run
The cooling fan runs when the power is supplied to the
inverter and the operation command is on. The cooling
fan stops when the power is supplied to the inverter
and the operation command is off. When the inverter
heat sink temperature is higher than its set value, the
cooling fan operates automatically regardless of its
operation status.
1
Always On
The cooling fan runs constantly if power is supplied to
the inverter.
2
Temp
Control
With power connected and the run operation
command on: if the setting is in Temp Control, the
cooling fan will not operate unless the temperature in
the heat sink reaches the set temperature.
Note
In 11
–
75 kW model types, if the heat sink temperature reaches a set level by input current
harmonic waves or noise, the cooling fan may run to protect the inverter even when ADV-64 is set
to “0 (During Run)”.
8.25
Input Power Frequency Settings
Select the frequency for inverter input power. If the frequency changes from 60 Hz to 50 Hz, all
other frequency (or RPM) settings, including the maximum frequency, base frequency, etc., will
change to 50 Hz. Likewise, changing the input power frequency setting from 50 Hz to 60 Hz will
change all related function item settings from 50 Hz to 60 Hz.
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
BAS
10
Input power
frequency
60/50 Hz Sel
0 60 Hz
0
–
1
-
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...