Learning Advanced Features
296
Operation in the event of fault trips
Fault trips
Auto restart after fault trips
Ground Trip, Over Current1, Over Voltage
Trip operation
H/W-Diag, Over Current2, Safety Opt Err
Fire mode operation voids the product warranty. To test fire mode not to increase the fire mode
operation count at ADV-83, set ADV-
80 to “2
-
Fire Test”
and operate the inverter.
If the multi-function terminal input set
to “51
(Fire Mode)
” is on
when ADV-83 is set to
“1
(Fire
Mode)
”
, the count value set at ADV-83 is increased by 1.
8.43
Dynamic Braking (DB) Resistor Operation
Reference Voltage
Depending on the capacity, the iS7 series is divided into models with a braking resistor circuit
integrated inside the inverter, and models that require an external braking unit to be installed.
The inverters rated between 0.75
–
22 kW have the built-in braking model (except for the brake
resistor), and the inverters rated above 30 kW require an external braking unit. Therefore, the
reference voltage setting function for the braking resistor is necessary for inverters rated
below 22 kW.
Group Code Name
LCD Display
Parameter
Setting
Setting Range
Unit
ADV
79
DB unit
operating
voltage
DB Turn On Lev
390 V
200 V Type: 350
–
400 V
V
780 V
400 V Type: 600
–
800 V
ADV-79 DB Turn On Lev
: This is the operation reference voltage for the braking resistor. The
braking resistor operates when the DC link voltage exceeds the reference value.
The initial value for 200 V-type inverters is 390 V, and the initial value for 400 V-type inverters is
780 V.
For 200 V-type inverters, the reference voltage that stops the braking resistor is 10 V lower than
the operating voltage set at ADV-79. For 400 V-type inverters, the braking resistor stops if the
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...