![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 192](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801192.webp)
Basic Functions
175
B
as
ic
Func
tio
ns
7.13
V/F (Voltage/Frequency) Control
Configure the inverter’s output voltages, gradient levels, and output patterns to achieve a
target output frequency with the V/F control. The amount of torque boost used during low
frequency operations can also be adjusted.
7.13.1
Linear V/F Pattern Operation
A linear V/F pattern configures the inverter to increase or decrease the output voltage at a fixed
rate for different operation frequencies based on V/F characteristics. A linear V/F pattern is
particularly useful when a constant torque load is applied.
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
DRV
09
Control mode
Control Mode
0
V/F
-
-
18
Base frequency Base Freq
60.00
30.00
–
400.00
Hz
19
Start frequency Start Freq
0.50
0.01
–
10.00
Hz
BAS
07
V/F pattern
V/F Pattern
0
Linear
-
-
Linear V/F Pattern Setting Details
Code
Description
DRV-18 Base Freq
Sets the base frequency.
A base frequency is the inverter’s output frequency
when running at its rated voltage. Refer to the motor’s rating plate to set this
parameter value.
DRV-19 Start Freq
Sets the start frequency. A start frequency is a frequency at which the inverter
starts voltage output. The inverter does not produce an output voltage while
the frequency reference is lower than the set frequency. However, if a
deceleration stop is made while operating above the start frequency, the
output voltage will continue until the operation frequency reaches a full stop (0
Hz).
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...