Table of Functions
440
No. Communi
-cation
Address
LCD Display Name
Setting Range
Initial
Value
Shift in
Opera-
tion
Page Control Mode
operation
1
Yes
* The grey cells indicate a hidden code which is only visible when setting a code.
Note 40)
PRT-10 codes are displayed only when PRT-
09(Retry Number) is set above “0”.
Note 41)
PRT-13
–
15 codes are displayed only when PRT-
12(Lost Cmd Mode) is not “None”.
Note 42)
PRT-32
–
33 codes are displayed only when PRT-
31(No Motor Trip is set as “Free
-
Run”.
13.12
Parameter Mode
–
2nd Motor Function Group
(
M2)
2nd Motor Function Group (PAR
M2)
No.
Communi
-cation
Address
LCD Display
Name
Setting Range Initial Value
Shift in
Opera-
tion
Page
Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
00 -
Jump Code
Jump code
0
–
99
14
O
-
O O X O X
04 0h1C04
M2-Acc Time
Acceleration time
0
–
600 (sec)
Below 75 kW 20.0 O
258 O O X O X
Above 90 kW 60.0
05 0h1C05
M2-Dec Time Deceleration time
0
–
600 (sec)
Below 75 kW 30.0 O
258 O O X O X
Above 90 kW 90.0
06 0h1C06
M2-Capacity
Motor capacity
0 0.2 kW
-
X
258 O O X O X
21 185 kW
07 0h1C07
M2-Base Freq Base frequency
30
–
400 (Hz)
60.00
X
258 O O X O X
08 0h1C08
M2-Ctrl Mode Control mode
0 V/F
0:V/F
X
258 O O X O X
1 V/F PG
2 Slip Compen
3 Sensorless-1
4 Sensorless-2
10 0h1C0A M2-Pole Num Motor pole
2
–
48
Dependent on
motor capacity
X
258 O O X O X
11 0h1C0B M2-Rated Slip Rated slip speed
0
–
3000 (rpm)
X
258 O O X O X
12 0h1C0C M2-Rated Curr Motor rated current 1.0
–
1000.0 (A)
X
258 O O X O X
13 0h1C0D M2-Noload Curr Motor no-load current 0.5
–
1000.0 (A)
X
258 O O X O X
14 0h1C0E
M2-Rated Volt Motor rated voltage 180
–
480 (V)
X
258 O O X O X
15 0h1C0F
M2-Efficiency
Motor efficiency
70
–
100 (%)
X
O O X O X
16 0h1C10
M2-Inertia Rt
Load inertia ratio
0
–
8
X
17 -
M2-Rs
Stator resistance
0
–
9.999 (
)
X
18 -
M2-Lsigma
Leak inductance
0
–
99.99 (mH)
X
19 -
M2-Ls
Stator inductance
0
–
999.9 (mH)
X
258 O O X O X
20 -
M2-Tr
Rotor time constant 25
–
5000 (ms)
X
258 O O X O X
25 0h1C19
M2-V/F Patt
V/F pattern
0 Linear
0:Linear
X
258 O O X O X
1 Square
2 User V/F
26 0h1C1A M2-Fwd Boost Forward torque boost 0
–
15 (%)
Below 75 kW: 2.0
Above 90 kW: 1.0
X
258 O O X O X
27 0h1C1B M2-Rev Boost Reverse torque boost 0
–
15 (%)
X
258 O O X O X
28 0h1C1C M2-Stall Lev
Stall prevention level 30
–
150 (%)
150
X
O O X O X
29 0h1C1D M2-ETH 1min Electronic thermal one 100
–
200 (%)
150
X
258 O O X O X
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...