Communication Function
356
Command Loss Protective Operation Setting Details
Code
Description
PRT-12 Lost Cmd
Mode,
PRT-13 Lost Cmd
Time
Select the operation to run when a communication error has occurred and
lasted exceeding the time set at PRT-13.
Setting
Function
0
None
The speed command immediately becomes the
operation frequency without any protection function.
1
Free-Run
The inverter blocks output. The motor performs in
free-run condition.
2
Dec
The motor decelerates and then stops.
3
Hold Input
Operates continuously with the speed of the inputted
speed command until the loss of the speed
command.
The inverter calculates the average input value for 10
seconds before the loss of the speed command and
uses it as the speed reference.
4
Hold Output Operates continuously with the operate frequency
before the speed loss. The inverter calculates the
average output value for 10 seconds before the loss
of the speed command and uses it as the speed
reference.
5
Lost Preset
The inverter operates at the frequency set at PRT-14
(Lost Preset F).
PRT-14 Lost Preset
F
Set the Lost Preset frequency that will be applied if PRT-12 (Lost Cmd Mode) is
set to
“
5 (Lost Preset).
”
Caution) If PRT-
13 (Lost Cmd Time) is set to “0.0” (sec), protection
features may be
activated even during a normal operation, depending on the type of command
source. To prevent this, appropriately set the lost command decision time.
11.7
Setting Virtual Multi-Function inputs
Multi-function input can be controlled using a communication address (0h0385). Set codes
COM-70
–
85 to the functions to operate, and then set the BIT relevant to the function to 1 at
0h0385 to operate it.
Group
Code
LCD Display
Parameter Setting
Unit
COM
70-85
Virtual DI x
0
None
-
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...