Table of Functions
408
Expansion Function Group (PAR
ADV)
No.
Communi-
cation
Address
LCD
Display
Name
Setting Range
Initial
Value
Shift in
Opera-
tion
Page
Control Mode
V
/
F
S
L
V
C
S
L
T
V
C
T
24 0h1318
Freq Limit Frequency limit
0 No
0:No X
188 O O O X X
1 Yes
25
Note
10
)
0h1319
Freq Limit
Lo
Frequency lower limit 0
–
upper limit (Hz)
0.50
O
188 O O O X X
26 0h131A
Freq Limit
Hi
Frequency upper limit 0.5
–
maximum frequency
(Hz)
60.00 X
188 O O O X X
27 0h131B
Jump Freq Frequency jump
0 No
0:No X
191 O O O X X
1 Yes
28
Note
11
)
0h131C
Jump Lo 1 Jump frequency lower
limit 1
0
–
jump frequency upper
limit 1 (Hz)
10.00 O
191 O O O X X
29 0h131D Jump Hi 1 Jump frequency upper
limit 1
Jump frequency lower limit
1
–
maximum frequency (Hz) 15.00 O
191 O O O X X
30 0h131E
Jump Lo 2 Jump frequency lower
limit 2
0
–
jump frequency
upper limit 2 (Hz)
20.00 O
191 O O O X X
31 0h131F
Jump Hi 2 Jump frequency upper
limit 2
Jump frequency lower limit
2
–
maximum frequency (Hz) 25.00 O
191 O O O X X
32 0h1320
Jump Lo 3 Jump frequency lower
limit 3
0-jump frequency
upper limit 3 (Hz)
30.00 O
191 O O O X X
33 0h1321
Jump Hi 3 Jump frequency upper
limit 3
Jump frequency lower limit
3
–
maximum frequency (Hz) 35.00 O
191 O O O X X
34
Note
10
)
0h1322
Jog Freq
Limit
Jog frequency limit
0
No
1:Yes O
189 O O O X X
1
Yes
41
Note
12
)
0h1329
BR Rls Curr Brake release current 0
–
180.0 (%)
50.0
O
280 O O O X X
42 0h132A
BR Rls Dly Brake release delay
time
0
–
10.00 (sec)
1.00
X
280 O O O X X
44 0h132C
BR Rls Fwd
Fr
Brake release
forward frequency
0
–
400 (Hz)
1.00
X
280 O O O X X
45 0h132D BR Rls Rev
Fr
Brake release
reverse frequency
0
–
400 (Hz)
1.00
X
280 O O O X X
46 0h132E
BR Eng Dly Brake engage delay
time
0
–
10 (sec)
1.00
X
280 O O O X X
47 0h132F
BR Eng Fr Brake engage
frequency
0
–
400 (Hz)
2.00
X
280 O O O X X
50 0h1332
E-Save
Mode
Energy saving
operation
0 None
0:None X
248 O O X X X
1 Manual
2 Auto
51
Note
13
)
0h1333
Energy
Save
Energy saving amount 0
–
30 (%)
0
O
248 O O O X X
60 0h133C
Xcel
Change Fr
Acc/dec time
transition frequency 0
–
maximum frequency (Hz) 0.00
X
170 O O O X X
* The grey cells indicate a hidden code which is only visible when setting a code.
Note 10)
ADV-25
–
26, 34 is displayed only when ADV-24
(Freq Limit) is set as “Freq Limit”.
Note 11)
ADV-28
–
33 is displayed only when ADV-27
(Jump Freq) is set as “Yes”.
Note 12)
ADV-41
–
47 is displayed only when a code of OUT-31
–
33 is set as “BR Control”.
Note 13)
ADV-51 is displayed only when ADV-50 (E-
Save Mode) is set as a value other than “None”.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...