Connecting the Cables
67
Inverter capacity
Terminal
screw size
Screw torque
1)
(Kgf·cm)
Cable
2)
Exterior fuse
mm²
AWG or kcmil
R,S,T
U,V,W R,S,T
U,V,W Current Voltage
220 kW M12
182.4
–
215.0 250
250
500
500
800 A
500 V
280 kW M12
182.4
–
215.0 325
325
650
650
1000 A 500 V
315 kW M12
182.4
–
215.0 2x200 2x200 2x400 2x400 1200 A 500 V
375 kW M12
182.4
–
215.0 2x250 2x250 2x500 2x500 1400 A 500 V
1) Apply rated torques to the terminal screws. Loose screws may cause the terminals to short circuit
and malfunction.
2) Only use copper wires with a 600 V, 75
℃
rating for the power terminal wiring.
4.7.1
Cable Length between the Inverter and the Motor
The maximum cable lengths of the inverter and the motor are listed in <Table 1) Maximum
cable length by inverter capacity>.
Make sure that the total cable length does not exceed 495 ft (150 m). For inverters with a
capacity of less than 3.7 kW, ensure that the total cable length does not exceed 165 ft (50 m).
Long cable runs can cause reduced motor torque in low frequency applications due to voltage
drop. Long cable runs also increase a circuit’s susceptibility to stray capacitance and may
trigger over-current protection devices, or result in the malfunction of equipment connected to
the inverter.
<Table 1) Maximum Cable Length by Inverter Capacity>
Inverter capacity
Up to 3.7 kW
5.5 kW or more
Maximum cable length
< 164 ft (50 m)
< 492 ft (150 m)
The following table lists maximum carrier frequencies available for model types with a rated
capacity of 5.5 kW or more.
<Table 2) Maximum Carrier Frequency according to Cable Length>
Distance
< 165 ft (50 m)
< 330 ft (100 m)
> 330 ft (100 m)
Allowed Carrier Frequency
<15 kHz
<5 kHz
<2.5 kHz
Depending on the system layout and operating conditions at the installation site, high peak
output voltage may result.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...