Basic Functions
192
7.19
2
nd
Operation Mode Setting
Apply two types of operation modes and switch between them as required. For both the first
and second command source, set the frequency after shifting operation commands to the
multi-function input terminal. Mode switching can be used to stop remote control during an
operation using the communication option and to switch the operation mode to operate via
the local panel, or to operate the inverter from another remote control location.
Select one of the multi-function terminals from codes IN-65
–
75 and set the parameter value to
“
15
(2nd Source)”.
Group Code
Name
LCD Display
Parameter Setting Unit
DRV
06
Command source
Cmd Source
1
Fx/Rx-1
-
07
Frequency reference source Freq Ref Src
2
V1
-
08
Torque reference source
Trq Ref Src
0
Keypad-1
BAS
04
2nd command source
Cmd 2nd Src
0
Keypad
-
05
2nd frequency reference
source
Freq 2nd Src
0
KeyPad-1
-
06
2nd torque reference source
Trq 2
nd
Src
0
Keypad-1
IN
65
–
75 Px terminal configuration
Px Define
(Px: P1
–
P8 [optional:
P9
–
P11])
15 2nd Source -
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...