![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 390](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801390.webp)
Communication Function
373
11.13.4
Expansion Common Area Parameter
11.13.4.1
Inverter Monitoring Area Parameter (Read only)
Address Parameter
Scale unit Assigned content by bit
0h0300 Inverter model
-
-
iS7: 000Bh
0h0301 Inverter capacity
-
-
0.75 kW: 3200h
1.5 kW: 4015h, 2.2 kW: 4022h, 3.7kW: 4037h,
5.5 kW: 4055h, 7.5 kW: 4075h, 11 kW: 40B0h
15 kW: 40F0h, 18.5 kW: 4125h, 22 kW: 4160h,
30 kW: 41E0h, 37 kW: 4250h, 45 kW: 42D0h
55 kW: 4370h, 75 kW: 44B0h, 90 kW: 45A0h
110 kW: 46E0h, 132 kW: 4840h, 160 kW: 4A00h
185 kW: 4B90h
0h0302
Inverter input voltage /
power supply type
(single phase, 3 phase)
/ cooling method
-
-
200 V single phase open air cooling: 0220h
200 V 3 phase open air cooling: 0230h
200 V single phase forced cooling: 0221h
200 V 3 phase forced cooling: 0231h
400 V single open air cooling: 0420h
400 V 3 phase open air cooling: 0430h
400 V single phase forced cooling: 0421h
400 V 3 phase forced cooling: 0431h
0h0303 Inverter S/W version
-
-
Ex.) 0x0100: Version 1.00
0x0101: Version 1.01
0h0304 Reserved
-
-
-
0h0305 Inverter operating status -
-
B15
0000(0) : Normal status
0100(4): Warning status
1000(8): Fault status (operates
according to set value of OUT-30 Trip
Out Mode)
B14
B13
B12
B11
-
B10
B9
B8
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...