246
Group Code Name
LCD Display
Parameter Setting Setting range Unit
stop level
Lev
86
Kinetic energy buffering
P-Gain
KEB P Gain
1500
0
–
20000
%
87
Kinetic energy buffering I
gain
KEB I Gain
500
1
–
20000
%
88
Kinetic energy buffering
slip gain
KEB Slip
Gain
30.0
0
–
2000.0
%
89
Kinetic energy buffering
acceleration time
KEB Acc
Time
10.0
0.0
–
600.0
Sec
IN
65
–
75
PX terminal setting
option
Px Define
50 KEB-1 Select 0
–
51
Kinetic Energy Buffering Operation Setting Details
Code
Description
CON-77
KEB Select
Select the kinetic energy buffering operation when the input power is
disconnected.
Note
If a multi-function terminal is set to
“
50 (KEB-1 Select)
”
, KEB operation is
available via terminal input only. Set CON-77 to
“
0 (none)
”
in this case.
Setting
Function
0 None
General deceleration is carried out until a low voltage trip
occurs.
1 KEB-1
If input power failure occurs, the inverter output frequency is
controlled and the regeneration energy from the motor is
charged by the inverter. Normal operation is resumed when
the power is supplied again, using the acceleration time set
at CON-89 (KEB Acc Time).
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...