![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 194](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801194.webp)
Basic Functions
177
B
as
ic
Func
tio
ns
7.13.3
User V/F Pattern Operation
The iS7 inverter allows the configuration of user-defined V/F patterns to suit the load
characteristics of a specific motor.
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
BAS
07
V/F pattern
V/F Pattern
2 User V/F
0
–
2
-
41
User frequency 1 User Freq 1
15.00
0
–
Maximum
frequency
Hz
42
User voltage 1
User Volt 1
25
0
–
100%
%
43
User frequency 2 User Freq 2
30.00
0
–
Maximum
frequency
Hz
44
User voltage 2
User Volt 2
50
0
–
100%
%
45
User frequency 3 User Freq 3
45.00
0
–
Maximum
frequency
Hz
46
User voltage 3
User Volt 3
75
0
–
100%
%
47
User frequency 4 User Freq 4
60
0
–
Maximum
frequency
Hz
48
User voltage 4
User Volt 4
100
0
–
100%
%
User V/F pattern Setting Details
Code
Description
BAS-41 User Freq 1
–
BAS-48 User Volt 4
Sets the parameter values to assign user-defined frequencies (User Freq x)
for the start and maximum frequencies. Voltages can also be set to
correspond with each frequency, and for each user voltage (User Volt x).
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...