![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 301](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801301.webp)
Learning Advanced Features
284
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
39
Interlock movement
delay time
Interlock DT
-
5.0
0.1
–
360.0
Sec
40
Aux motor rotation
pressure difference
Actual Pr Diff
-
2
0
–
100%
%
41
Main motor
acceleration time
when the number of
pumps decreases
Aux Acc Time
-
2.0
0.0
–
600.0
Sec
42
Main motor
deceleration time
when the number of
pumps increases
Aux Dec Time
-
2.0
0.0
–
600.0
Sec
OUT
31
–
33
Multi-function relay,
Multi-function
output 1
Relay x or Q1
24
MMC
-
-
34
–
36
Qx terminal
configuration
Qx Define
24
MMC
-
-