Using Monitor Functions
314
9.4
Relay Output and Multi-function Output Terminal
Settings
Group
Code
LCD Display
Parameter Setting
Unit
OUT
30
Trip Out Mode
-
010
bit
31
Relay 1
28
Trip
-
32
Relay 2
14
Run
-
33
Q1 Define
1
FDT-1
34
–
36
Relay 3
–
5
-
-
-
41
DO Status
-
-
bit
Relay Output and Multi-function Output Terminal Setting Details
Code
Description
OUT-30 Trip
Out Mode
Set OUT-30 (Trip Out Mode) to enable or disable the fault relay.
Bit on
Bit off
Setting option
Function
Bit3
Bit2
Bit1
The top-right corner of the display is
‘Bit 1’
.
Operates when a low voltage fault trip occurs.
Operates when a fault trip other than low voltage occurs.
Operates when auto restart fails (PRT-08
–
09).
OUT-31
Relay1,
OUT-32,
Relay2,
OUT-33 Q1
Define,
OUT-34
–
36
Relay 3
–
5
Set output options for the relays and multi-function output terminal Q1.
Setting
Function
0
None
No output signal
1
FDT-1
Inspects whether the output frequency for the inverter
reaches the frequency set by the user. The inverter begins
to operate when the condition is met:
Absolute value
(set frequency - output frequency) <
detected frequency width/2.
When the detected frequency width is 10 Hz, the FDT-1
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...