Using Monitor Functions
Code
Description
24 Load Speed
Displays the load speed in the desired scale and unit.
Displays the load speed as values which are applied
in the units of rpm or mpm set in ADV-63 (Load Spd
Unit), ADV-61 (Load Spd Gain), and ADV-62 (Load Spd
Scale).
25 Temperature
Displays the inverter’s internal temperature.
9.1.2
Displaying Output Power
Mode
Group
Code
LCD Display
Parameter Setting
Unit
PAR
BAS
18
Trim Power %
-
100.0
%
When CNF-21
–
23 (Monitor Line-x Select) is set to
“4
(Output Power)
”
, increase the set value at
BAS-18 (Trim Power) appropriately if the output power displayed on the keypad is lower than
expected.
If the output power displayed on the keypad is higher than expected, decrease this set value
accordingly. The output power display is calculated using voltage and current. However, an
output power error may occur when the power factor is low.
Note
WHour Counter (Inverter power consumption)
Values are calculated using voltage and current. Electric power is calculated every second and the
results are accumulated.
Power consumption is displayed as follows:
•
Less than 1,000 kW: Units are in kW, displayed in a 999.9 kW format.
•
1
–
99 MW: Units are in MW, displayed in a 99.99 MWh format.
•
100
–
999 MW: Units are in MW, displayed in a 999.9 MWh format.
•
More than 1,000 MW: Units are in MW, displayed in 9,999 MWh format and can be displayed up
to 65,535 MW. (Values exceeding 65,535 MW will reset the value to 0 and units will return to
kW. It will be displayed in a 999.9 kW format).
•
If the WH CNF-62 (Count Reset) is set to
“
YES,
”
you can clear the electricity consumption.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...