Using Protection Features
334
Code
Description
PRT-05 Phase Loss
Chk
When open-phase protection is operating, input and output configurations
are displayed differently. When the LCD segment is On, the corresponding
bit is set to ‘Off’.
Item
Bit status (On)
Bit status (Off)
Keypad
display
Setting
Keypad
display
Function
Bit 2 Bit 1
Output open-phase protection. If one or more
than one phase from U, V, and W is open, the
inverter output will be blocked and
“
Out Phase
Open
”
will be displayed on the keypad.
Input open-phase protection. If one or more
phases from R, S, and T are open, the inverter
output will be blocked and
“
In Phase Open
”
will
be displayed on the keypad. Protection against
input phase open starts only when a certain
amount of current (70
–
80% of the inverter-rated
output current) flows through the motor.
Input and output open-phase protection
PRT-06 IPO V Band
Sets the band of the allowed ripple voltage. If one or more phases from the
inverter output are open, the ripple of the DC link voltage increases. If ripple
voltage exceeds the set ripple voltage band, an input phase open trip occurs.
The IPO V Band may be adjusted depending on the operating environment.
Sets the IPO V Band 1
–
10 volts higher if the output load is too large for the
input capacity, and an open phase fault trip occurs during a normal
operation.
Sets the IPO V Band 1
–
10 volts lower if the output load is too smaller for the
input capacity.
Note
Ensure that the motor-rated current (BAS-13 Rated Curr) is correctly set. Phase open protection may
not be operated properly i
f the motor’
s rated current is not correctly set at BAS-13.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...