Learning Advanced Features
Adv
anc
ed
Feat
ur
es
237
Note
Sensorless-2 vector control mode is greatly affected by the motor and load characteristics.
Therefore, it is sometimes necessary to adjust the controller gain values.
When a sensorless-2 vector control is operated in speed mode [DRV-10 (torque control) is set to
“0
(No)
”
. If the operation is unstable at extremely low speeds (below 2
–
3 Hz), or if the speed bounces
during startup, increase the CON-22 (ASR-SL I Gain1) value to 200% of the default value. With a
regenerative load, motor torque ripples may occur frequently. In this case, decrease the CON-21
(ASR-SL P Gain1) value to 50% of the default value. If this does not solve the problem, increase the
CON-21 (ASR-SL P Gain1) value back to the default, and decrease the CON-30 (S-Est I Gain1) value to
50% of the default value.
8.13
Vector Control Mode Operation
With an optional encoder module installed to the inverter, vector control mode provides highly
precise operation abilities.
Similar to sensorless-1 and sensorless-2 vector control modes, vector control mode requires
motor parameter values for operation. Before operating the inverter in sensorless-2 mode, run
auto tuning first.
Group Code
Name
LCD Display
Parameter Setting
Unit
DRV
09
Control mode
Control Mode
5 Vector
-
21
Speed unit
selection
Hz / rpm Sel
1 Rpm Display
-
BAS
20
Auto tuning
Auto Tuning
1 All
-
CON
09
Initial excitation time
PreExTime
-
1.0
sec
10
Initial excitation power supply
Flux Force
-
100.0
%
11
Continued operation duration
Hold Time
-
1.0
sec
12
Speed controller proportional
gain 1
ASR P Gain 1
-
50.0
%
13
Speed controller integral gain 1 ASR I Gain 1
-
300
ms
15
Speed controller
proportional gain 2
ASR P Gain 2
-
50.0
%
16
Speed controller integral gain 2 ASR I Gain 2
-
300
ms
18
Gain exchange frequency
Gain Sw Freq
-
0.00
Hz
19
Gain exchange time
Gain Sw Delay
-
0.10
sec
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...