Learning Advanced Features
Adv
anc
ed
Feat
ur
es
247
Code
Description
2 KEB-2
If input power failure occurs, the inverter output frequency is
controlled and the regeneration energy from the motor is
charged by the inverter. The motor decelerates and stops
when the power is supplied again, using the deceleration
time set at DRV-04 (Dec Time).
CON-78
KEB Start Lev,
CON-79
KEB Stop Lev
Sets the start and stop points of the kinetic energy buffering operation. The set
values must be based on the low voltage trip level at 100%, and the stop level
(CON-79) must be set higher than the start level (CON-78).
CON-86
KEB P Gain
Used to maintain the voltage during the kinetic energy buffering operation. It
operates the inverter by modifying the set value to prevent malfunctions
caused by low voltage after power interruptions.
CON-87
KEB I Gain
Used to maintain the voltage during the kinetic energy buffering operation.
Sets the gain value to maintain the operation until the frequency stops during
the kinetic energy buffering operation.
CON-88
KEB Slip Gain
Used to prevent malfunctions caused by low voltage from initial kinetic energy
buffering occurring due to power interruptions.
CON-89
KEB Acc Time
Sets the acceleration time for the frequency reference when the inverter’s
operation becomes normal after the kinetic energy buffering operation.
IN-65
–
75 Px
Define
Sets a multi-function input Px to
“
50 (KEB-1 Select)
”
.
If the terminal is on during an operation, the inverter operates in KEB-1 mode.
The inverter output frequency is controlled to the output level set at CON-78
and the regeneration energy from the motor is charged by the inverter.
Normal operation is resumed when the power is supplied again, using the
acceleration time set at CON-89 (KEB Acc Time).
If the terminal is not on, KEB operation does not start when the input power
failure occurs.
If a multi-function terminal is set to
“
50 (KEB-1 Select)
”
, KEB operation is
available via terminal input only. Set CON-77 to
“
0 (none)
”
in this case.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...