Learning Advanced Features
274
Code
Description
OUT-55
TimerOn Delay,
OUT-56
TimerOff Delay
Inputs a signal (On) to the timer terminal to operate a timer output
(Timer out) after the time set at OUT-55 has passed. When the multi-
function input terminal is off, the multi-function output or relay turns off
after the time set at OUT-56.
8.35
Auto Sequence Operation
Create operation sequences that can be automatically run using terminal inputs. You can
configure up to two sequences for automated inverter operation.
Group Code
Name
LCD Display
Parameter Setting
Setting Range Unit
APP
01
Applied function
selection
APP Mode
4
Auto Sequence 0
–
4
-
IN
65
–
75
Px terminal
configuration
Px Define
(Px: P1
–
P8
[optional:
P9
–
P11])
41 SEQ-1
0
–
51
-
42 SEQ-2
43 Manual
44 Go Step
45 Hold Step
OUT
31
–
32
Multi-function relay
1
–
2
Relay 1
–
2
20 Step Pulse
-
-
33
Multi-function
output 1
Q1 Define
21 Seq Pulse
-
-
AUT
01
Auto operation
type
Auto Mode
0
Auto-A
-
1
Auto-B
02
Auto operation
terminal delay time
Auto Check
-
0.10
0.02-2.00
Sec
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...