Peripheral Devices
102
5.1.5
Indicators on the DB unit
On a DB unit, there are three LED indicators (one red and two green indicators) that indicate
the operating condition of the DB unit.
Indicator
name
Color
Location
Description
Power
indicator
Red
Middle
Turns on when the main power is supplied to the unit (if a DB
unit is connected to an inverter, the power indicator is turned
on when the main power is supplied to the inverter).
RUN
indicator
Green
Right
Turns on when the DB unit is regenerating.
OHT
indicator
Green
Left
Turns on when the overheating protection function is
enabled.
If the DB unit temperature exceeds the maximum allowed
operating temperature, the overheating protection function
is activated to cut off the input to the DB unit (the power
indicator on the DB unit is turned off).
5.1.6
DB Resistors
The following table lists type A DB unit specifications for your reference. For type B and type C
DB unit specifications, refer to the instruction manuals that are supplied with the DB units.
Before installing a DB resistor, refer to the instruction manuals provided by the manufacturer
to choose an appropriate type of DB resistor.
Note
When you double the duty cycle (%ED) of a DB unit, the wattage ratings of the optional DB resistor
must be doubled accordingly.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...