Basic Functions
184
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
12
Start DC braking
time
DC-Start Time 0.00
0.00
–
60.00
sec
13
DC Injection Level DC Inj Level
50
0
–
200
%
The amount of DC braking required is based on the motor’s rated current. Do not use DC braking
resistance values that can cause current draw to exceed the rated current of the inverter. If the DC
braking resistance is too high or brake time is too long, the motor may overheat or be damaged.
7.17
Stop Mode Setting
Select Stop mode to stop the inverter operation.
7.17.1
Deceleration Stop
Deceleration stop is a general stop mode. If there are no extra settings applied, the motor
decelerates to 0 Hz and stops, as shown in the figure below.
Group Code
Name
LCD Display
Parameter Setting Setting Range Unit
ADV
08
Stop mode
Stop Mode
0
Dec
-
-
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...