7.1.3.1
Setting a Frequency Reference for 0
–
10 V Input
Set IN-
06 (V1 Polarity) to “0
(unipolar)”. Use a voltage output from an external source or use the
voltage output from the VR terminal to provide inputs to V1. Refer to the diagrams below for
the wiring required for each application.
[External source application]
[Internal source (VR) application]
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
DRV
07
Frequency reference
source
Freq Ref Src 2
V1
0
–
9
-
IN
01
Frequency at
maximum analog
input
Freq at 100%
Maximum
frequency
0.00
–
max. frequency Hz
05
V1 input monitor
V1
Monitor[V]
0.00
0.00
–
10.00
V
06
V1 polarity options
V1 Polarity
0
Unipolar
0
–
1
-
07
V1 input filter time
constant
V1 Filter
10
0
–
10000
ms
08
V1 minimum input
voltage
V1 volt x1
0.00
0.00
–
10.00
V
09
V1 output at
minimum voltage (%)
V1 Perc y1
0.00
0.00
–
100.00
%
10
V1 maximum input
voltage
V1 Volt x2
10.00
0 .00
–
10.00
V
11
V1 output at
maximum voltage
(%)
V1 Perc y2
100.00
0
–
100
%
16
Rotation direction
options
V1 Inverting 0
No
0
–
1
-
17
V1 quantizing level
V1
Quantizing
0.04
0.00*, 0.04
–
10.00
%
*
Quantizing is disabled if “0” is selected.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...