211
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
ADV
20
Dwell frequency
during acceleration
Acc Dwell Freq 5.00
Start frequency
–
Maximum
frequency
Hz
21
Operation time
during acceleration
Acc Dwell Time 0.0
0.0
–
60.0
sec
22
Dwell frequency
during deceleration
Dec Dwell Freq 5.00
Start frequency
–
Maximum
frequency
Hz
23
Operation time
during deceleration
Dec Dwell Time 0.0
0 .0
–
60.0
sec
Note
Dwell operations are not performed when:
•
The dwell operation time is set to 0 sec or the dwell frequency is set to 0 Hz.
•
Re-acceleration is attempted from a stop or during deceleration, since only the first acceleration
dwell operation command is valid.
[Acceleration dwell operation]