Connecting the Cables
85
4.18.3
Checking the Inverter Operation
Using an inverter, you can easily operate a motor at a high speed. Before operating a motor using
an inverter, ensure that the set speed is within the motor's rated speed.
Follow the instructions to ensure that the motor operates correctly according to the inverter
settings, and adjust the settings if required.
1
Set DRV-06 (CMD source) to
“
0 (KEYPAD).
”
2
Set DRV-07 (Freq Ref Src) to
“
0 (Keypad-1).
”
3
Set DRV-01 (CMD Frequency) to a temporary speed (Ex: 60 Hz).
4
Press the FWD key on the keypad, and ensure that the motor is rotating in the correct
direction. When the forward command (Fx) is on, the motor should rotate
counterclockwise when viewed from the load side of the motor. If the motor rotates in the
reverse direction, switch the cables at the U and V terminals.
Ensure that the input power is within the inverter’s rated input voltage range during op
eration.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...