Using Protection Features
335
10.2.2
External Trip Signal
Set one of the multi-function input
terminals to “4
(External Trip)
”
to allow the inverter to stop
operation when abnormal operating conditions arise.
Group
Code
LCD Display
Parameter Setting
Unit
IN
65
–
72
Px Define
4
External Trip
-
87
DI NC/NO Sel
-
(000 0000000)
-
External Trip Signal Setting Details
Code
Description
IN-87 DI NC/NO
Sel
Select the type of input contact. If the mark of the switch is at the bottom (0), it
operates as a form A terminal (Normally Open). If the mark is at the top (1), it
operates as a form B terminal (Normally Closed).
The corresponding terminals for each bit are as follows:
Bit
11
10
9
8
7
6
5
4
3
2
1
Terminal -
-
-
P8
P7
P6
P5
P4
P3
P2
P1
10.2.3
Inverter Overload Protection (IOLT)
If more current than the inverter-rated current flows, the protective function starts to protect
the inverter depending on the inverse time characteristic.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...