Basic Functions
152
7.1.6
Setting a Frequency Reference via RS-485 Communication
Control the inverter with upper-level controllers, such as PCs or PLCs, via RS-485
communication. Set DRV-07
(Frequency reference source) to “6 (Int 485)” and use the RS
-485
signal input terminals (S+/S-/SG) for communication. For more details, refer to
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
DRV
07
Frequency reference
source
Freq Ref Src 6
Int 485
0
–
9
-
COM
01
Integrated RS-485
communication
inverter ID
Int485 St ID -
1
1
–
250
-
02
Integrated
communication
protocol
Int485 Proto
0
ModBus RTU
0
–
2
-
1
ModBus
ASCII
2
LS Inv 485
04
Integrated
communication speed
Int485
BaudR
3
9600 bps
1200
–
38400
bps
04
Integrated
communication frame
configuration
Int485 Mode
0
D8/PN/S1
0
–
3
-
1
D8/PN/S2
2
D8/PE/S1
3
D8/PO/S1