Learning Advanced Features
Adv
anc
ed
Feat
ur
es
243
Note
•
Basic parameters for inverter operation must be correctly set before you can operate the
inverter in torque control mode.
•
Torque control is not available during low speed regeneration and light load operation. Operate
the inverter in vector control mode instead.
•
Do not switch between Fx and Rx operations while the inverter is operating in torque control
mode. An overcurrent or reverse deceleration fault trip may occur as a result.
Torque Control
–
Details
Code
Description
DRV-08 Trq Ref
Src
Select the input source for the torque reference.
Setting
Description
0
Keypad-1 Sets the torque reference using the keypad (up to 180%
of rated motor torque, set at CON-02).
1
Keypad-2
2
V1
Sets the torque reference using the analog terminals.
The torque reference changes based on the set value at
IN-02 (Torque at 100%).
For example, if IN-02 is set to 200%, the torque reference
becomes 200% when 20 mA current is supplied.
The setting can be viewed in monitor mode. Set CFG-06
–
08 to
“
19 (Torque Ref)
”
.
3
I1
6
Int485
Sets the torque reference using the built-in RS485
communication device.
CON-02 CMD
Torque
Sets the torque reference for keypad input.
IN-02 Torque at
100%
Sets the torque reference for analog terminal input.
CON-35 SL2 L-
ExcitLmt
This is the ratio to improve the operating characteristics in the low torque/low
speed range by lowering the magnetic flux current. However, if the value is set
too low, stable sensorless control may not be possible.
CON-62 Speed
Lmt Src
Select the input source for the speed limit.
Setting
Description
0
Keypad-1 Sets the speed limit using the keypad (CON-63 FWD
Speed Lmt / CON-64 REV Speed Lmt).
1
Keypad-2
2
V1
Set the torque reference using the analog terminals, in
the same manner as setting a frequency reference.
The setting can be viewed in monitor mode. Set CNF-21
–
23 to
“
23 (Speed Limit)
”
.
3
I1
6
Int485
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...