Communication Function
363
ENQ
Station ID CMD
Address
Number of Addresses SUM
EOT
05h
‘01’
‘R’
‘3000’
‘1’
‘A7’
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
2 bytes
1 byte
Note
Broadcasting
Broadcasting sends commands to all inverters connected to the network simultaneously. When
commands are sent from station ID 255, each inverter acts on the command regardless of the
station ID. However no response is issued for commands transmitted by broadcasting.
Error operation
For two or more data communications, when an error occurs as a result of the previous data
communication, the current data communication can be made normally regardless of the error
occurred as a result of the previous data communication.
11.13.1.1
Detailed Read Protocol
Read Request
Reads successive n words from address XXXX.
ENQ
Station ID CMD
Address
Number of Addresses SUM
EOT
05h
‘01’–’
1
F’
‘R’
‘XXXX‘
‘1’–‘8’ = n
‘XX’
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
2 bytes
1 byte
Total bytes=12. Characters are displayed inside single quotation marks(‘).
Read Normal Response
ACK
Station ID
CMD
Data
SUM
EOT
06h
‘01’–‘
1
F’
‘R’
‘XXXX’
‘XX’
04h
1 byte
2 bytes
1 byte
n x 4 bytes
2 bytes
1 byte
Total bytes= (7 x
n
x 4): a maximum of 39
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...