Learning Advanced Features
282
8.38
Multi-function Output On/Off Control
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
ADV
66
Output contact
On/Off control
options
On/Off Ctrl Src 1
V1
0
–
4
-
67
Output contact
point On level
On-C Level
-
90.00
10
–
100
%
68
Output contact
point Off level
Off-C Level
-
10.00
0
–
Output
contact on level
%
OUT
31
–
33
Multi-function
relay, Multi-
function output 1
Relay x or Q1
34
On/Off
Control
-
-
Multi-function Output On/Off Control Details
Code
Description
ADV-66 On/Off Ctrl Src
ADV-67 On-C Level
ADV-68 Off-C Level
If the analog input value exceeds the set value, the output relay or
multi-function output terminal can be turned on or off.
Select the analog input to use for On/Off control at ADV-66 and set
the levels at which the output terminal is on and off at ADV-67 and
68 respectively.
If the analog input value exceeds the value set at ADV-67, the
output terminal is on. If the analog input is below the value set at
ADV-68, the output terminal is off.
8.39
MMC function
The MMC (Multiple Motor Control) function is used to control multiple motors of a pump
system. The main motor connected with the inverter output is controlled by the PID controller.
The auxiliary motors are connected with the supply power and turned on and off by the relay
within the inverter.
The relay for controlling auxiliary motors uses Relay 1 and 2 in the standard I/O module
embedded in the inverter and multi-function output terminal Q1. If the I/O expansion option
module is connected to the inverter option slot, up to 3 relay outputs can be used.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...