Using Protection Features
344
10.2.11
Fan Fault Detection
Group
Code
LCD Display
Parameter Setting
Unit
PRT
79
FAN Trip Mode
0
Trip
-
OUT
31
–
32
Relay 1,2
8
FAN Warning
-
33
Q1 Define
Fan Fault Detection Setting Details
Code
Description
PRT-79 Fan Trip Mode
Set the cooling fan fault mode.
Setting
Function
0
Trip
The inverter output is blocked and the fan trip is
displayed when a cooling fan error is detected.
1
Warning
When OUT-36 (Q1 Define) or OUT-31
–
35 (Relay1, 2)
is
set to “8 (FAN Warning)”
, the fan error signal is
output and the operation continues.
OUT-33 Q1 Define,
OUT-31
–
32 Relay1, 2
When the code value is set to “8 (FAN Warning)”
, the fan error signal is
output and operation continues. How
ever, when the inverter’s in
ternal
temperature rises above a certain level, output is blocked due to activation
of overheat protection.
10.2.12
Low Voltage Fault Trip
Group
Code
LCD Display
Parameter Setting
Unit
PRT
81
LVT Delay
-
0.0
sec
OUT
31
–
32
Relay 1,2
11
Low Voltage
-
33
Q1 Define
Low Voltage Fault Trip Setting Details
Code
Description
PRT-81 LVT Delay
When inverter input power is lost and the internal DC link voltage drops
below a certain voltage level, the inverter will block the output and a low
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...