Basic Functions
149
B
as
ic
Func
tio
ns
Group Code
Name
LCD Display Parameter Setting
Setting Range Unit
maximum V2’
voltage
46
Invert V2 rotational
direction
V2 Inverting No
No/Yes
-
47
V2 quantizing level
V2
Quantizing
0.04
0.00*, 0.04
–
10.00
%
*
Quantizing is disabled if “0” is selected.
7.1.4.2
Setting a Reference Frequency using Input Current at I2 Terminal
Set the DRV-
07 (Frequency reference source) to “
5 (I
2)” and apply an input voltage of
0
–
20 mA
to the I2 terminal.
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
DRV
07
Frequency reference
source
Freq Ref Src 5
I2
0
–
9
-
50
I2 input monitor
I2 Monitor
0.00
0.00
–
20.00
mA
52
I2 input filter time
constant
I2 Filter
10
0
–
10000
ms
53
I2 minimum input
current
I2 Curr x1
4.00
0.00
–
20.00
mA
54
I2 output at
minimum current (%)
I2 Perc y1
0.00
0
–
100
%
55
I2 maximum input
current
I2 Curr x2
20.00
4.00
–
20.00
mA
56
I2 output at
maximum current (%)
I2 Perc y2
100.00
0.00
–
100.00
%
61
I2 rotation direction
options
I2 Inverting 0
No
0
–
1
-
62
I2 quantizing level
I2
Quantizing
0.04
0.00*, 0.04
–
10.00
%
*
Quantizing is disabled if “0” is selected.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...