Learning Advanced Features
292
8.40
Press Regeneration Prevention (To evade control
operation in the status of regeneration during
press)
Press regeneration prevention is used during press operations to prevent braking during the
regeneration process. If motor regeneration occurs during a press operation, the motor
operation speed automatically goes up to avoid the regeneration zone.
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
ADV
73
Regeneration
evasion mode
RegenAvd Mode 000-111
001
Bit
74
Regeneration
evasion function
for press
selection
RegenAvd Sel
0
No
0
–
1
-
75
Press
regeneration
prevention
operation
voltage level
RegenAvd Level
350
200 V class: 300
–
400
V
700
400 V class: 600
–
800
76
Press
regeneration
prevention
compensation
frequency limit
CompFreq Limit 1.00
0
–
10.00
Hz
77
Press
regeneration
prevention P-
Gain
RegenAvd Pgain 50.0
0
–
100.0
%
78
Press
regeneration
prevention I gain
RegenAvd Igain 500
20
–
30,000
ms
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...