![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 392](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801392.webp)
Communication Function
375
Address Parameter
Scale unit Assigned content by bit
0h0308 Keypad Title version
-
-
0x0101: Version 1.01
0h0309 -
0h30F
Reserved
-
-
-
0h0310 Output current
0.1 A
-
0h0311 Output frequency
0.01 Hz
-
0h0312 Output RPM
0
RPM -
0h0313 Motor feedback speed
0
RPM -32768rpm - 32767rpm (Having a polarity.)
0h0314 Output voltage
1
V
-
0h0315 DC Link voltage
1
V
-
0h0316 Output power
0.1 kW -
0h0317 Output torque
0.1 %
Exception: It is not calculated during V/F
control.
0h0318 PID reference
0.1 %
-
0h0319 PID feedback
0.1 %
-
0h031A Number of No.1 motor
display
-
-
Number of No.1 motor display
0h031B
Number of No.2 motor
display
-
-
Number of No.2 motor display
0h031C
Number of selected
motor display
-
-
Number of selected motor display
0h031D Selection among Hz/rpm -
-
0: Hz unit
1: rpm unit
0h031E
-0h031F
Reserved
-
-
-
0h0320 Digital input information -
-
BI5
Reserved
BI4
Reserved
BI3
Reserved
BI2
Reserved
BI1
Reserved
BI0
P11 (I/O expansion)
B9
P10 (I/O expansion)
B8
P9 (I/O expansion)
B7
P8 (Basic I/O)
B6
P7 (Basic I/O)
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...