Peripheral Devices
88
Inverter
Capacity
Wiring Switch
Short Circuit Switch
Electronic Contactor
METASOL
SUSOL
Model
Rated
current[A]
Model
Rated
current[A]
Model
Rated
current[A]
Model
Rated
current[A]
0900iS7-4 ABS403c 400
UTS400 400
EBS403c
400
MC-330a
330
1100iS7-4 ABS603c 500
UTS600 500
EBS603c
500
MC-400a
400
1320iS7-4 ABS603c 630
UTS600 600
EBS603c
630
MC-400a
400
1600iS7-4 ABS603c 630
UTS600 600
EBS603c
630
MC-630a
630
1850iS7-4 ABS803c 800
UTS800 800
EBS803c
800
MC-630a
630
2200iS7-4 ABS803c 800
UTS800 800
EBS803c
800
MC-800a
800
2800iS7-4 ABS1003b 1000
UTS1200 1000
EBS1003c 1000
1000A
1000
3150iS7-4 ABS1203b 1200
UTS1200 1200
EBS1203c 1200
1200A
1200
3750iS7-4 1400A
1400
1400A
1400
1400A
1400
1400A
1400
Only use Class H or RK5 UL listed input fuses and UL listed breakers. See the table above for the
voltage and current ratings for the fuses and breakers.
Utiliser
UNIQUEMENT des fusibles d’entrée homologués de Classe H ou RK5 UL et des disjoncteurs
UL. Se reporter au tableau ci-dessus pour la tension et le courant nominal des fusibless et des
disjoncteurs.
Note
•
If you install the recommended reactors, you can maintain the power factor above 85%, and
keep the THD below 40% for operations at the rated load. Improvements are reduced at lighter
loads.
•
Cable impedance affects the input power factor and occurrence of harmonic waves. The input
power factor and THD improvement of the reactors may be lower depending on the
transformer capacity, the transformer impedance, and the cable length.
•
Refer to the specifications table and install recommended reactors. Although a higher
inductance value (L) of the reactor results in an improvement in the power factor and better
suppression of harmonic effects, power loss increases at the same time due to voltage drop.
•
The capacity of built-in DC reactors in some iS7 inverter models is based on the normal duty
load factor. Therefore, improvements may be reduced during a heavy duty operation.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...