Basic Functions
148
7.1.4
Setting a Frequency Reference Using an I/O Expansion
Module (Terminal V2/I2)
After installing an optional I/O I/O expansion moduleto the iS7 inverter, you can set and modify
a frequency reference using the input voltage or current at the V2/I2 terminal.
7.1.4.1
Setting a Reference Frequency using Input Voltage at V2 Terminal
Set the DRV-
07 (Frequency reference source) to “4 (V2)” and apply an input voltage of
-10
–
+12 V
to the V2 terminal.
Group Code
Name
LCD Display Parameter Setting
Setting Range Unit
DRV
07
Frequency
reference source
Freq Ref Src 4
V2
0
–
9
-
IN
35
V2 input display
V2 Monitor 0.00
-10.00
–
+10.00
V
37
V2 input filter time
constant
V2 Filter
10
0
–
10000
ms
38
Minimum V2 input
voltage
V2 Volt x1
0.00
0.00
–
10.00
V
39
Output% at
minimum V2
voltage
V2 Perc y1
0.00
0.00
–
100.00
%
40
Maximum V2 input
voltage
V2 Volt x2
10.00
0.00
–
10.00
V
41
Output% at
maximum V2
voltage
V2 Perc y2
100.00
0.00
–
100.00
%
42
Minimum V2 input
voltage’
V2 -
Volt x1’
0.00
0
–
10
V
43
Output% at
minimum V2
voltage’
V2 -
Perc y1’
0.00
0
–
100
%
44
Maximum V2 input
voltage’
V2 -
Volt x2’
-10.00
0
–
10
V
45
Output% at
V2 -
Perc y2’
-100.00
-100
–
0
%
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...