Basic Functions
185
B
as
ic
Func
tio
ns
7.17.2
Stop after DC Braking
When the operation frequency reaches the set value during deceleration (DC braking
frequency) the inverter stops the motor by supplying DC power to the motor. With a stop
command input, the inverter begins decelerating the motor. When the frequency reaches the
DC braking frequency set at ADV-17, the inverter supplies DC voltage to the motor and stops it.
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
ADV
08
Stop mode
Stop Mode
0
Dec
0
–
4
-
14
Output block time
before braking
DC-Block Time 0.10
0.00
–
60.00
sec
15
DC braking time
DC-Brake Time 1.00
0
–
60
sec
16
DC braking amount
DC-Brake Level 50
0
–
200
%
17
DC braking frequency DC-Brake Freq 5.00
0.00
–
60.00
Hz
Note
DC braking does not produce stop torque. Install appropriate peripheral devices if stop torque is
required in your application.
DC Braking After Stop Setting Details
Code
Description
ADV-14 DC-Block
Time
Sets the time to block the inverter output before DC braking. If the inertia of the
load is great, or if the DC braking frequency (ADV-17) is set too high, a fault trip
may occur due to overcurrent conditions when the inverter supplies DC voltage
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...