Using Protection Features
347
10.2.16
No Motor Trip
Group Code No.
LCD Display
Parameter Setting
Setting Range Unit
PRT
31
No Motor Trip
0
None
-
-
32
No Motor Level
5
1
–
100
%
33
No Motor Time
3.0
0.1
–
10.0
sec
No Motor Trip Setting Details
Code
Description
PRT-32 No Motor Level,
PRT-33 No Motor Time
If the output current value [based on the rated current (BAS-13)] is lower
than the value set at PRT-32 (No Motor Level), and if this continues for
the time set at PRT-
33 (No Motor Time), a “no motor trip”
occurs.
If BAS-
07 (V/F Pattern) is set to “1 (Square)”, set P
RT-32 (No Motor Level) to a value lower than the
factory
default. Otherwise, “
No Motor T
rip” due to a lack of output current will result when the ‘
No
Motor T
rip’
operation is set.
10.2.17
Low Voltage Fault Trip 2 During Operation
Group
Code
LCD Display
Parameter Setting range
Unit
PRT
82
Low Voltage2
00~11
00 : default
Bit
If input power is disconnected during inverter operation and internal DC voltage decreases
lower than a certain voltage, the inverter disconnects the o
utput and displays low voltage “2 ”
on the keypad.
Even if the voltage increases and goes back to the normal state, unlike a low voltage fault, it
remains in a fault state until the user unlocks the fault state.
If PRT-
82 (LV2 Enable) is set to “01,” and if the input power is disconnected during inverter
operation and the internal DC voltage drops to lower than a certain voltage, the inverter stops
output and displays “Low Voltage2.” Unlike the low voltage trip (L
ow Voltage), the low voltage 2
(Low Voltage2) trip will not be reset even after the internal DC voltage of the inverter has
recovered to above the trip level. Therefore, you must reset the inverter to reset the trip. The
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...