![LS ELECTRIC SV-iS7 Series Скачать руководство пользователя страница 333](http://html1.mh-extra.com/html/ls-electric/sv-is7-series/sv-is7-series_user-manual_1943801333.webp)
Using Monitor Functions
316
Code
Description
Group Code LCD Display
Initial Setting
Unit
OUT
57
FDT Frequency -
30.00
Hz
58
FDT Band (Hz)
-
10.00
Hz
4
FDT-4
The output signal can be separately set for acceleration
and deceleration conditions.
•
In acceleration:
Operation frequency
≧
Detected
frequency
•
In deceleration:
Operation frequency > (Detected
frequency - Detected frequency width/2)
Detected frequency width is 10 Hz. When the detected
frequency is set to 30 Hz, FDT-4 output is as shown in the
graph below.
Group Code LCD Display
Parameter
setting
Unit
OUT
57
FDT Frequency -
30.00
Hz
58
FDT Band (Hz)
-
10.00
Hz
5
Over Load
Outputs a signal at motor overload.
6
IOL
Outputs a signal when the inverter input current exceeds
the rated current and a protective function is activated to
prevent damage to the inverter, based on inverse
proportional characteristics.
7
Under Load
Outputs a signal at load fault warning.
8
Fan Warning Outputs a signal at fan fault warning.
9
Stall
Outputs a signal when a motor is overloaded and stalled.
Содержание SV-iS7 Series
Страница 17: ......
Страница 22: ...About the Product 5 1 2 2 Interior and Exterior View IP 54 Model Types Less than 22 kW 200 400 V ...
Страница 114: ...Peripheral Devices 97 Group 2 ...
Страница 115: ...Peripheral Devices 98 Group 3 ...
Страница 116: ...Peripheral Devices 99 Group 4 ...
Страница 153: ...Using the Keypad 136 The Parameter Initialization option is displayed again when the initialization is complete ...
Страница 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Страница 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...