Learning Advanced Features
248
Code
Description
•
Depending on the duration of instantaneous power interruptions and the amount of load
inertia, a low voltage trip may occur even during a kinetic energy buffering operation.
•
Motors may vibrate during kinetic energy buffering operation for some loads, except for
variable torque loads (for example, fan or pump loads).
8.18
Energy Saving Operation
8.18.1
Manual Energy Saving Operation
If the inverter output current is lower than the current set at BAS-14 (Noload Curr), the output
voltage must be reduced as low as the level set at ADV-51 (Energy Save). The voltage before the
energy saving operation starts will become the base value of the percentage. The manual
energy saving operation will not be carried out during acceleration and deceleration.
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
ADV
50
Energy saving
operation
E-Save Mode 1
Manual
0 None
-
1 Manual
2 Auto
51
Energy saving
amount
Energy Save 30
0
–
30
%
Содержание SV-iS7 Series