B629 Remote diagnostics
Parameter FUNCTION DB / OFF
In this parameter, the function of the remote diagnosis DB is activated.
Parameter Reference run ON / OFF
A reference travel can be made to determine the sensor data.
Parameter Start Reference run
The start time for the reference travel can be entered here (Every day – every week – 2x week).
B630 Evacuation Liquid Pit
Parameter: Evacuation Liquid Pit
By activating the parameter Liquid-Pit, an evacuation drive can be initiated by interrupting the + 24V
DC at the input with the input function E974 on the processor system. A water sensor or float switch is
recommended as a sensor for triggering. The output function A635 reports the status of the sensor
and the evacuation "liquid pit" is active.
This means that a corresponding text can be switched on the TFT. When the evacuation floor is
reached, the error “F258 flood pit” is triggered as long as the error persists. The message "LIQUID
PIT" is output via the LED matrix on the FKR (V00.030) and on the ER2013 / 14 with the new software
version 00.010.
Parameter: Evacuation Liquid Pit – Floor
The evacuation level is freely selectable. The second level is selected as the standard value. This must
be adapted to the conditions on site.
Parameter: Evacuation Liquid Pit – Entrance Open
The door position after arriving at the evacuation level can be set in this parameter. If there is only one
side of the door, the door is always open. If there are two door sides, it can be decided whether only
door side 1 or only door side 2 or both doors are open.
B630 Evacuation Gas
Parameter: Evacuation Gas
By activating the evacuation gas parameter, an evacuation drive can be initiated by interrupting the +
24V DC at the input with the input function E997 on the processor system. A special gas sensor or a
central trigger is recommended for triggering. The output function A636 reports the state that the gas
evacuation drive is active.
This message is available as scrolling text "Evacuation gas" from FKR613 (V00.030) and on the
ER2013 / 14 from V00.010.
Parameter:
Evacuation Gas
– Floor
The evacuation level is freely selectable. The second level is selected as the standard value. This must
be adapted to the conditions on site. The output function A637 reports the state that the gas evacuation
level has been reached.
Parameter: Evacuation Gas – Entrance Open
The door position after arriving at the evacuation level can be set in this parameter. If there is only one
side of the door, the door is always open. If there are two door sides, it can be decided whether only
door side 1 or only door side 2 or both doors are open.
Содержание DAVID 613
Страница 1: ...OPERATING MANUAL LIFT CONTROLLER SYSTEM DAVID 613 FUNCTIONS START UP INSTRUCTIONS...
Страница 2: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 2...
Страница 7: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 7 8 INDEX 263...
Страница 10: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 10...
Страница 12: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 12...
Страница 13: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 13...
Страница 14: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 14...
Страница 34: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 34...
Страница 35: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 35...
Страница 98: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 98...
Страница 124: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 124 Unit shaft copying system...