Page - 154 -
Parameter Guide mode - call request
If the guide mode is active, the outside call requests are displayed flashing on the outside call ac-
knowledgment and on the corresponding inside call acknowledgment. The flashing mode, differenti-
ated between inside and outside, can be set here.
B614 HOTEL OBLIGATION STOP
PARAMETER: HOTEL-OBLIGATION STOP
You can choose between:
-
Upward
During all upward trips which were started below the main entrance level an obligation stop is
operated in the main entrance level. At expiration of the driving on time on car call the trip
continues to goal floor.
-
Downward
During all downward trips which were started below the main entrance level an obligation stop
is operated in the main entrance level. At expiration of the driving on time on car call the trip
continues to goal floor.
-
Upward and Downward
Functions like by upward and downward
The interior advantages code switch is operated in the car ist the function hotel obligation stop despite
activation out of operation.
615 TIME REALY
PARAMETER: TIME RELAY 1
By attitude of the operating kind
Time relay 1
and definition of the activation entrance
Entrance time
relay-1
and switching exit
Exit time relay-1
in the easily programmable entrances and exits of the menu
B7) it is possible to solve further auxiliary functions at elevators.
You can choose between:
-
Suit-retarded
The switch-on delay is adjustable in its time.
-
Waste-retarded
The switch-off delay is adjustable in its time.
-
Suit-retarded with impulse
The switch-on delay and the length of the impulse are adjustable
-
Waste-retarded with impulse
The switch-off delay and the length of the impulse are adjustable.
DECELERATION TIME RELAY- 1
In this parameter the deceleration time can be stopped the suit and/or the waste of the time relay 1. The
range of adjustment extends from 0,5 to 600 sec.
IMPULSE TIME RELAY-1
In this parameter can be positioned the temporal pulse time delay relay 1. The range of adjustment
extends from 05, to 600 sec.
PARAMETER TIME RELAY-2
Equivalent one to the function under the time relay-1.
DECELERATION TIME RELAY- 1
Equivalent one to the function under the time relay-1.
IMPULSE TIME RELAY-2
Equivalent one to the function under the time relay-1.
SPEEDLIMIT Vx
You can put a speedlimit Vx at which an output function goes active.
TIMER 1-10
You can choose up to 10 timers.
Timer-1: Switch-on time-1
Start-1 at
xx:xx h
Switch-off time-1
Stop-1 at
xx:xx h
Switch-on time-2
Start-2 at
xx:xx h
Содержание DAVID 613
Страница 1: ...OPERATING MANUAL LIFT CONTROLLER SYSTEM DAVID 613 FUNCTIONS START UP INSTRUCTIONS...
Страница 2: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 2...
Страница 7: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 7 8 INDEX 263...
Страница 10: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 10...
Страница 12: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 12...
Страница 13: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 13...
Страница 14: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 14...
Страница 34: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 34...
Страница 35: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 35...
Страница 98: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 98...
Страница 124: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 124 Unit shaft copying system...