KW Aufzugstechnik GmbH OPERATING MANUAL DAVID-613
DAVID-D613-V125-E 13.04.2021
Page - 149 -
B609 – EMERGENCY POWER SERVICE
Emergency evacuation in case of individual drivers
Is the emergency evacuation activated for a single driver, only the 230 signal at input 401 is evaluated.
230V AC means normal operating level, 0V is the AC means failure, the car moves to the preset emer-
gency level and set the door of the door opening side.
Exterior and interior control are disabled. More actions only after ranking. Come on the 230V AC level
again to the input 401, the system automatically returns to normal operation.
The input 401 has been assigned before-standard input function with the E01-emergency oper-
ation. You can also program any other input to this function.
Emergency evacuation of sequential circuit
The emergency evacuation is activated with sequential circuit, so only the 230V AC signal at input 401
and evaluated at the entrance to 402nd Input. Input 401 is again the message line. Input 402 is the
entrance for the beginning of the emergency trip.
The level at 230V AC input 401 means normal operation. 0V is the AC means failure and only then is
the input evaluated 402nd
The 230V AC level at input 402 is the start of the emergency drive. This means when the input 401 is
energized. 0V AC means waiting for the emergency trip. The emergency operation begins when input
401 is energized.
Lies on a 230V AC input 402 then level at, so the car goes into the emergency level set and opens the
door to the set side door. Exterior and interior control is disabled.
After reaching the emergency level, the relay 403, the voltage 402 continues to the next elevator, so
that it can reach the evacuation level.
Did our elevator, receive the signal 402 at the beginning of the emergency trip, but as any errors the
door do not close, then after a set time the relay is activated 403, to give other elevators the chance to
evacuate.
More actions only after ranking. Come on the 230V AC level at the input 401 again, the system auto-
matically returns to normal operation.
The input 401 "A08-emergency level reached" standard with the input function "E01-emergency
mode", the input 402 with the "E02-emergency travel" and the output relay K307 with the preset
function. You can also program any other input and output of these functions.
PARAMETER: ENERGENCY POWER SERVICE
In this parameter you can activate the function of the emergency power service. The options are:
1.) Power generator ( with emergency diesel generators, UPS or onsite ).
2.) Battery Power ( With an evacuation unit specifically for the elevator system )
3.) With brake open ( UPS opens and closes the brakes again when they reach the zone area by
car )
4.) EVA90 drive with speed Ve, up to the zone, then switch to speed V0.
PARAMETER: FLOOR
The floor of the emergency power service is freely chosen. The standard value is the first floor.
PARAMETER: ENTRANCE OPEN
In this parameter the door open can be adjusted after arrival at the evacuation level. With only one side
of the door basically the door is always open. On two sides of existing door can be decided whether only
the door-side or only one side of the door-2 or both doors are open.
PARAMETER: FOLLOW-CIRCUIT
If this parameter is enabled, it waits before starting the evacuation trip to the input function E02-emer-
gency travel.
PARAMETER: PIECO BUZZER
If you activate this parameter the piezo buzzer of the carpanel-unit ITR can switch on, if there is an
emergency power service travel.
PARAMETER: FOLLOW-CIRCUIT-DEADTIME
The set time is available to the elevator to reach the emergency level. If it is not him, it is locked and
the output 403 (A08-output function emergency level reached), the voltage switches to the input 402 of
the next lift.
Содержание DAVID 613
Страница 1: ...OPERATING MANUAL LIFT CONTROLLER SYSTEM DAVID 613 FUNCTIONS START UP INSTRUCTIONS...
Страница 2: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 2...
Страница 7: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 7 8 INDEX 263...
Страница 10: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 10...
Страница 12: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 12...
Страница 13: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 13...
Страница 14: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 14...
Страница 34: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 34...
Страница 35: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 35...
Страница 98: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 98...
Страница 124: ...KW Aufzugstechnik GmbH OPERATING MANUAL DAVID 613 DAVID D613 V125 E 13 04 2021 Page 124 Unit shaft copying system...