Application Guide - NP900 Series
57 (504
)
A996A
Figure 3.2.1.4-33. Delayed pick-up release, delay counter value is decreasing during the
release time.
Resetting characteristics can be set according to the application. Default setting is
delayed with 60 ms and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the
operating time during the release time, function will not trip if the input signal is not
activated again during the release time counting.
3.2.1.5
S
TAGE FORCING
In NP900 series relays it is possible to test the logic and the operation of the protection
system of the relay by controlling the state of the protection functions by hand without
injecting any current into the relay. To enable stage forcing set the
Enable stage forcing
to
Enabled
in
General
menu. After this it is possible to control the status of a protection
function (Normal, Start, Trip, Blocked etc.) in the
Info
page of the function.
NOTE: When Stage forcing is enabled protection functions will change state also by user
input, injected currents/voltages also affect the behavior of the relay. It is still advised to
disable Stage Forcing after testing has ended.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...