Application Guide - NP900 Series
363 (504
)
A996A
Table 3.5.3.2-224 Environmental settings
Name
Range
Step
Default
Description
Object max temp (tmax =
100%)
0…500 deg
1 deg
90
Maximum allowed temperature for
the protected object. Default setting
is +90 degrees and it suits for Celsius
range and for PEX insulated cables
Ambient temp sel
0: Manual set
1: RTD
-
0:Manual
set
Selection whether fixed or measured
ambient temperature should be used
for the thermal image biasing.
Man.Amb.Temp.Set
0…500 deg
1 deg
15 deg
Manual fixed ambient temperature
setting for the thermal image biasing.
For underground cables commonly is
used 15 degrees Celsius. Setting is
visible if Ambient temp sel is set to
“Manual set”.
RTD Amb.Temp.Read
0…500 deg
1 deg
15 deg
RTD ambient temperature reading for
the thermal image biasing. Setting is
visible if Ambient temp sel is set to
“RTD”.
Ambient lin. or curve
0:Linear est.
1:Set curve
-
0:Linear
est
Selection of ambient temperature
correction either by internally
calculated compensation based into
end temperatures or user settable
curve. Default setting is 0:Linear corr,
which means internally calculated
correction for ambient temperature.
Temp.reference (tref)
k
amb
=1.0
-60…500 deg
1 deg
15 deg
Temperature reference setting. In this
temperature manufacturer
presumptions apply and the thermal
correction factor is 1.00 (rated
temperature). For ground dug cables
this is usually 15
̊
C and in air 25
̊
C.
Setting is visible if Ambient lin. or
curve is set to “Linear est.”
Max ambient temp
0…500 deg
1 deg
45 deg
Maximum ambient temperature
setting. If measured temperature is
more than maximum set temperature
the set correction factor for maximum
temperature shall be used. Setting is
visible if Ambient lin. or curve is set
to “Linear est.”
k at max amb temp
0.01…5.00 xIn
0.01 xIn 1.00 xIn
Temperature correction factor for
maximum ambient temperature
setting. Setting is visible if Ambient
lin. or curve is set to “Linear est.”
Min ambient temp
-60…500 deg
1 deg
0 deg
Minimum ambient temperature
setting. If measured temperature is
less than minimum set temperature
the set correction factor for minimum
temperature shall be used. Setting is
visible if Ambient lin. or curve is set
to “Linear est.”
k at min amb temp
0.01…5.00 xIn
0.01 xIn 1.00 xIn
Temperature correction factor for
minimum ambient temperature
setting. Setting is visible if Ambient
lin. or curve is set to “Linear est.”
Amb.Temp.ref1...10
-50.0…500.0
deg
0.1 deg
15 deg
Temperature reference points for the
user settable ambient temperature
coefficient curve. Setting is visible if
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...