Figure 3.6.5.4-201 Example of timers and pick-up parameters. No CLPU pick up since
too short current low situation.
CLPU does not activate even current has been under
ILow
. The time setting
Tset
is not
exceed and therefore no CLPU signal is issued
.
If the CLPU is wanted to be activated in
shorter time or directly when the measured current is below the
ILow
setting the
Tset
parameter can be set to lower value and even to 0.000s delay for immediate operation.
Figure 3.6.5.4-202 Example of timers and pick-up parameters. Activated CLPU instant
release due to overcurrent.
CLPU activates after current has been under
ILow
setting for time
Tset .
When current
exceed the IHigh setting the maximum allowed CLPU timer start to count until
Tmax
time.
In this example the measured current is exceeding the
IOver
setting during the startup
situation and causes the CLPU signal immediate release.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...