Application Guide - NP900 Series
223 (504
)
A996A
TM> is activated and in use.
Safe stall time
cold
0.1…600.0s
0.1s
20.0s
MST
TM> (49M)
Ist> (48)
Im> (50M)
N> (48)
Safe stall time when motor is cold. If
this value is not informed then set to
same than hot stall time. This leads
most probably to overprotection with
cold motor stall but is best guess in
such case. This setting value is
used for the cold thermal stall curve
selection in automatic control. Also
motor start-up and number of starts
calculations use this parameter.
Safe stall time
hot
0.1…600.0s
0.1s
15.0s
MST
TM> (49M)
Ist> (48)
Im> (50M)
N> (48)
Safe stall time when motor is hot.
This setting value is used for the hot
thermal stall curve selection in
automatic control. Also motor start-
up and number of starts calculations
use this parameter.
Starts when cold 1…100 st
1 st
3 st
MST
N> (48)
Allowed starts per x hours for cold
motor.
Starts when hot
1…100 st
1 st
2 st
MST
N> (48)
Allowed starts per x hours for hot
motor.
Starts in hours
1…100h
1h
1h
MST
N> (48)
Hours when the allowed given hot
and cold starts applies.
Min time betw.
starts
0.1…600.0s
0.1s
20.0s
MST
N> (48)
Minimum time in between of starts
or start attempts.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...