Application Guide - NP900 Series
173 (504
)
A996A
Name
Description
Range
Default
Measured
magnitude
Decision which
calculated
voltage is
supervised
U1 Pos seq.Volt
U2 Neg seq.Volt
U1 Pos
seq.Volt
Reset ratio of 97 % in over voltage applications is inbuilt in the function and is always
related to the
Uset
value. Reset ratio of 103 % in under voltage applications is inbuilt in
the function and is always related to the
Uset
value. When Uc exceed/decrease
above/below the Uset value will cause pick-up operation of the function.
Table 3.2.16.4-118 Pick-up characteristics setting
Name
Description
Range
Step
Default
Pick-up
terms
Decision if the
function will pick-up
when the monitored
voltage is under or
over the set pick-up
value.
Over >
Under<
-
Over>
Uset
Pick-up setting
5.00…150.00 % Un 0.01%Un 105%Un
Ublk
Under voltage
blocking (visible when
Pick-up term is
Under<
0.00…80.00 % Un
0.01%Un 5%Un
The pick-up activation of the function is not directly equal to start-signal generation of the
function. Start signal is allowed if blocking condition is not active.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...