Application Guide - NP900 Series
107 (504
)
A996A
Figure 3.2.9-48 Simplified function block diagram of the CBFP function.
3.2.9.1
M
EASURED INPUT VALUES
Function block uses analog current measurement values. Function uses always the
fundamental frequency magnitude of the current measurement input. For residual current
measurement I01, I02 or calculated I0 can be selected. -20ms averaged value of the
selected magnitude is used for pre-fault data registering.
Table 3.2.9.1-79 Analogic magnitudes used by the CBFP function.
Signal
Description
Time base
IL1RMS
Fundamental RMS measurement of phase L1/A current
5 ms
IL2RMS
Fundamental RMS measurement of phase L2/B current
5 ms
IL3RMS
Fundamental RMS measurement of phase L3/C current
5 ms
I01RMS
Fundamental RMS measurement of residual input I01
5 ms
I02RMS
Fundamental RMS measurement of residual input I02
5 ms
I0Calc
Calculated residual current from the phase current inputs
5 ms
DOIN
Monitoring of the digital output relay status
5 ms
DIIN
Monitoring of digital input status
5 ms
Selection of the used AI channel is made with a setting parameter. In all possible input
channel variations pre-fault condition is presented with 20 ms averaged history value from
-20 ms of Start or Trip event.
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...
Страница 504: ...Application Guide NP900 Series 504 504 A996A A996A...