Application Guide - NP900 Series
355 (504
)
A996A
Table 1.1.1.10-215 Calculations of the DIF function.
Name
Description
L1Bias
Calculated phase L1 Bias current
L2Bias
Calculated phase L2 Bias current
L3Bias
Calculated phase L3 Bias current
L1Diff
Calculated phase L1 Differential current
L2Diff
Calculated phase L2 Differential current
L3Diff
Calculated phase L3 Differential current
L1Char
Calculated phase L1 Max differential current allowed with current bias level
L2Char
Calculated phase L2 Max differential current allowed with current bias level
L3Char
Calculated phase L3 Max differential current allowed with current bias level
HV I0d> Bias current
Calculated HV side restricted earth fault Bias current
HV I0d> Diff current
Calculated HV side restricted earth fault Differential current
HV I0d> Char current
Calculated HV side restricted earth fault differential current allowed with current bias
level
LV I0d> Bias current
Calculated LV side restricted earth fault Bias current
LV I0d> Diff current
Calculated LV side restricted earth fault Differential current
LV I0d> Char current
Calculated LV side restricted earth fault differential current allowed with current bias
level
Table 1.1.1.10-216. Output signals of the TRF function
Name
Description
Idb> Bias Trip
Trip output signal from the biased differential stage
Idi> Nobias Trip
Trip output signal from the non-biased/non-blocked differential stage
Idb> Bias Blocked
Blocked output from the biased differential stage (external blocking)
Idi> Bias Blocked
Blocked output from the non-biased/non-blocked differential stage (external blocking)
Idb> 2
nd
harm block on
Output of 2
nd
harmonic activation signal
Idb> 5
th
harm block on
Output of 5
th
harmonic activation signal
HV I0d> Trip
Trip output signal from the biased restricted earth fault differential stage HV side
HV I0d> Trip
Blocked output signal from the biased restricted earth fault differential stage HV side
LV I0d> Trip
Trip output signal from the biased restricted earth fault differential stage LV side
LV I0d> Trip
Blocked output signal from the biased restricted earth fault differential stage LV side
Содержание NP900 Series
Страница 1: ......
Страница 49: ...Application Guide NP900 Series 49 504 A996A Figure 3 2 1 3 25 Definite time operating characteristics...
Страница 50: ...Application Guide NP900 Series 50 504 A996A Figure 3 2 1 3 26 IEC predefined characteristics NI VI LTI and EI...
Страница 52: ...Application Guide NP900 Series 52 504 A996A Figure 3 2 1 3 28 IEEE predefined characteristics EI MI and VI...
Страница 243: ...Application Guide NP900 Series 243 504 A996A Figure 3 3 2 1 122 NPS biased thermal trip curves with kNPS values 7 and 10...
Страница 491: ...Application Guide NP900 Series 491 504 A996A 3 7 5 6 SETTING EXAMPLE...